Excerpt from the datasheet: Technical data FC-GPCS-RIO16-PF
| Supply | ||
|---|---|---|
| Connection | TV3: terminals 2, 4(+); 1, 3(-) | |
| Nominal voltage | 24 V DC, taking into account the rated voltage of the insulators used | |
| Voltage drop | 0.9V, voltage drop across the series diode on the terminal block must be taken into account. | |
| pulsation | ≤ 10% | |
| Merger | 4 A, in each case for 16 modules | |
| Power dissipation | ≤ 500 mW, without modules | |
| Reverse polarity protection | Yes | |
|
Redundancy |
||
| Supply | Redundancy is available. Power to the isolators is isolated, monitored, and protected by fuses. | |
|
Fault indication output |
||
| Connection | TV4: terminals 1, 2 | |
| Output type | potential-free contact | |
| Switch behavior |
no fault: relay contact closed power supply failure: relay contact is open |
|
| Contact loading | 30 VDC, 1 A | |
|
Indicators/settings |
||
| Display elements |
Supply1 LED (Power Supply Connector Board), Green LED Supply2 LED (Power Supply Connector Board), Green LED Error Status LED (malfunction indication), red LED - LED is on: power supply failure |
|
|
Compliance with the directive |
||
| Electromagnetic compatibility |
|
|
|
|
Directive 2014/30/EU | EN 61326-1:2013 (industrial premises) |
|
Correspondence |
||
| Electromagnetic compatibility |
NE 21:2017 For more information, see the system description. |
|
| Degree of protection | IEC 60529:2001 | |
|
Environmental conditions |
||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
|
Mechanical characteristics |
||
| Degree of protection | IP20 | |
| Connection |
|
|
|
|
Side of the field | hazardous area: push-in screw terminals, blue |
|
|
Control side | non-hazardous area: 37-pin Sub-D connector |
|
|
Supply | removable screw terminals, black |
|
|
Malfunction output | removable screw terminals, black |
| Cross-section of the core | Screw terminals: 0.25–2.5 mm2 (24–12 AWG) | |
| Material | body: polycarbonate | |
| weight | approx. 830 g | |
| Dimensions | 273 x 155 x 153 mm (10.7 x 6.1 x 6.0 in) (W x H x D) depth including module assembly | |
| Installation | on a 35 mm DIN rail in accordance with EN 60715:2001 | |
|
Data for use in hazardous areas |
||
| EC Type Examination Certificate | SESI 06 ATEX 022 | |
|
|
Marking |
II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
|
| Safe zone |
|
|
|
|
Maximum safe voltage | 250 V (Note: U m is not the nominal voltage.) |
| Certificate | DEMKO 18 ATEX 2116 X | |
|
|
Marking |
II 3G Ex ec nC IIC T4 Gc
|
| Galvanic isolation |
|
|
|
|
Excitation circuit/control circuit | safe electrical insulation in accordance with IEC/EN 60079-11, peak voltage 375 V |
| Compliance with the directive |
|
|
|
|
Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020, EN 60079-7:2015+A1:2018, EN 60079-11:2012, EN 60079-15:2010, EN 50303:2000 |
|
International certificates |
||
| UL approval | E106378 | |
|
|
Control drawing | 116-0327 |
| IECEx certification |
|
|
|
|
IECEx certificate |
IECEx CES 06.0003 IECEx UL 18.0111 X |
|
|
IECEx marking |
[Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I Ex ec nC IIC T4 Gc |
II (1)G [Ex ia Ga] IIC