Technical data of the KCD2-STC-Ex1-Y1
| Main Features | ||
|---|---|---|
| Signal type | Analog input | |
|
Parameters related to functional safety |
||
| Safety Integrity Level (SIL) | SIL 2 | |
| Systematic ability (SC) | SC 3 | |
|
Supply |
||
| Connection | Power bus or terminals 9+, 10- | |
| Nominal voltage | 19 ... 30 V DC current | |
| pulsation | ≤ 10% | |
| Rated current | ≤ 45 mA at 24 V and 20 mA output in source mode | |
| Power dissipation | ≤ 800 mW | |
| Power consumption | ≤ 1.1 W | |
|
Entrance |
||
| Connection side | side of the field | |
| Connection | terminals 1+, 2- | |
| Input signal | 4 ... 20 mA limited to approx. 26 mA | |
| Open circuit voltage/short circuit current | 22 V / 26 mA | |
| Available voltage | ≥ 15 V at 20 mA; ≥ 18 V at 4 mA | |
|
Exit |
||
| Connection side | control side | |
| Connection |
terminals 5-, 6+ terminals 5-, 8+ for HART resistor |
|
| Load | 0 ... 350 Ohm (source mode) | |
| Output signal |
source mode: 4...20 mA or 1...5 V (internal resistor: 250 Ohm, 0.1%) drain mode: 4 ... 20 mA, operating voltage 10 ... 30 V For additional internal or external loads (e.g. terminal +8) a voltage drop must be taken into account, e.g. 250 Ohm x 20 mA = 5 V. |
|
| pulsation | 20 mV rms | |
|
Transmission characteristics |
||
| Deviation |
at 20 °C (68 °F) < 0.1% of full scale, including nonlinearity and hysteresis (source mode and drain mode 4 ... 20 mA) ≤ ± 0.2% incl. nonlinearity and hysteresis (1...5 V source mode) |
|
|
|
The influence of ambient temperature |
< 2 μA/K (-20...70 °C (-4...158 °F)); < 4 μA/K (-40...-20 °C (-40...-4 °F)) (source mode and sink mode 4...20 mA) < 0.5 mV/K (-20...-4 °F) 70 °C (-4 ... 158 °F)); < 1 mV/K (-40...-20 °C (-40...-4 °F)) (1...5 V source mode) |
| Frequency range |
from the field side to the control side: bandwidth with 0.5 V pp signal 0 ... 3 kHz (-3 dB) control side field side: bandwidth with 0.5 V pp signal 0 ... 3 kHz (-3 dB) |
|
| Settlement time | ≤ 50 ms | |
| Rise time/fall time | ≤ 10 ms | |
|
Galvanic isolation |
||
| Input, output | Basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff. | |
| Input/Power | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff. | |
| Output/Power | Basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff. | |
|
Indicators/settings |
||
| Display elements | LED | |
| Controls | DIP switch | |
| Configuration | via DIP switches | |
| Marking | marking space at the front | |
|
Compliance with the directive |
||
| Electromagnetic compatibility |
|
|
|
|
Directive 2014/30/EU | EN 61326-1:2013 (industrial premises) |
|
Correspondence |
||
| Electromagnetic compatibility |
NE 21:2017 EN 61326-3-2:2018 |
|
| Degree of protection | IEC 60529:2001 | |
| Protection against electric shock | UL 61010-1:2012 | |
|
Environmental conditions |
||
| Ambient temperature | -40...70 °C (-40...158 °F) | |
|
Mechanical characteristics |
||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| weight | approx. 100 g | |
| Dimensions | 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 in) (W x H x D), case type A2 | |
| Installation | on a 35 mm DIN rail in accordance with EN 60715:2001 | |
|
Data for use in hazardous areas |
||
| EU Type Examination Certificate | CESI 06 ATEX 021 | |
|
|
Marking |
II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
|
|
|
Entrance | Ex iа |
| Supply |
|
|
|
|
Maximum safe voltage | 250 V AC (Note: U m is not the nominal voltage.) |
| Equipment | terminals 1+, 2- | |
|
|
Voltage | 25.2 V |
|
|
Current | 100 mA |
|
|
Power | 630 MW |
|
|
Internal capacity | 5.7 nF |
|
|
Internal inductance | minor |
| Certificate | CESI 19 ATEX 021 X | |
|
|
Marking |
II 3G Ex ec IIC T4 Gc
|
| Galvanic isolation |
|
|
|
|
Input, output | safe electrical insulation in accordance with IEC/EN 60079-11, peak voltage 375 V |
|
|
Input/Power | safe electrical insulation in accordance with IEC/EN 60079-11, peak voltage 375 V |
| Compliance with the directive |
|
|
|
|
Directive 2014/34/EU | EN 60079-0:2012+A11:2013, EN 60079-11:2012, EN 60079-7:2015 |
|
International certificates |
||
| UL approval | E106378 | |
|
|
Control drawing | 116-0459 (cULus) |
| IECEx certification |
|
|
|
|
IECEx Certificate | IECEx CES 06.0001X |
|
|
IECEx marking |
[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex ec IIC T4 Gc |
II (1)G [Ex ia Ga] IIC