Technical specifications of the KCD0-SD-Ex1.1245.SP
| Main Features | ||
|---|---|---|
| Signal type | Digital output | |
|
Parameters related to functional safety |
||
| Safety Integrity Level (SIL) | SIL 3 | |
|
Supply |
||
| Nominal voltage | loop powered | |
| Power dissipation | < 1 W | |
|
Entrance |
||
| Connection side | control side | |
| Connection | terminals 5, 6 | |
| Nominal voltage | 19 ... 30 V DC current | |
| Current |
≤ 72 mA at U i = 19 V, ≤ 50 mA at U i = 30 V with an output load of 265 Ohm ≤ 45 mA at U i = 19 V, ≤ 31 mA at U i = 30 V with shorted output ≤ 14 mA at U i = 19 V, ≤ 11 mA at U i = 30 V without load at the output |
|
| Inrush current | ≤ 200 mA after 100 µs | |
|
Exit |
||
| Connection side | side of the field | |
| Connection | terminals 1+, 2- | |
| Internal resistor | Max. 238 Ohm | |
| Current | ≤ 45 mA | |
| Voltage | ≥ 12 V | |
| Open circuit voltage | min. 22.7 V | |
| Output rated operating current | 45 mA | |
| Output signal | These values are valid for a rated operating voltage of 19 ... 30 V DC. | |
| On/Off Delay | Single operation: typical 1.7 ms/50 μs; Periodic: typical 5 μs/50 μs | |
|
Galvanic isolation |
||
| Input, output | reinforced insulation according to EN 50178, rated insulation voltage 300 V, eff. | |
|
Indicators/settings |
||
| Display elements | LED | |
| Marking | marking space at the front | |
|
Compliance with the directive |
||
| Electromagnetic compatibility |
|
|
|
|
Directive 2014/30/EU | EN 61326-1:2013 (industrial premises) |
|
Correspondence |
||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Protection against electric shock | UL 61010-1 | |
|
Environmental conditions |
||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
|
Mechanical characteristics |
||
| Degree of protection | IP20 | |
| Connection | spring terminals | |
| weight | approx. 100 g | |
| Dimensions | 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 in) (W x H x D), case type A2 | |
| Installation | on a 35 mm DIN rail in accordance with EN 60715:2001 | |
|
Data for use in hazardous areas |
||
| EU Type Examination Certificate | BASEEFA 06 ATEX 0170 | |
|
|
Marking |
II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC , I (M1) [Ex ia Ma] I
|
|
|
Exit | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
|
|
Voltage | 25.2 V |
|
|
Current | 110 mA |
|
|
Power | 693 MW |
| Entrance |
|
|
|
|
Maximum safe voltage | 250 V (Caution! Nominal voltage may be lower.) |
| Certificate | PF 06 CERTIFICATION 0971 X | |
|
|
Marking |
II 3G Ex nA IIC T4 Gc
|
| Galvanic isolation |
|
|
|
|
Input, output | safe electrical insulation in accordance with IEC/EN 60079-11, peak voltage 375 V |
| Compliance with the directive |
|
|
|
|
Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020, EN 60079-11:2012, EN 60079-15:2010 |
|
International certificates |
||
| FM approval |
|
|
|
|
Control drawing | 116-0419 (cFMus) |
| UL approval |
|
|
|
|
Control drawing | 116-0420 (cULus) |
| IECEx certification |
|
|
|
|
IECEx Certificate | IECEx BAS 06.0032 |
|
|
IECEx marking | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
II (1)G [Ex ia Ga] IIC ,