Excerpt from the datasheet: technical characteristics of the KCD2-SOT-Ex2
| Main Features | ||
|---|---|---|
| Signal type | Digital input | |
|
Parameters related to functional safety |
||
| Safety Integrity Level (SIL) | SIL 2 | |
| Systematic ability (SC) | SC 3 | |
|
Supply |
||
| Connection | Power bus or terminals 9+, 10- | |
| Nominal voltage | 19 ... 30 V DC current | |
| pulsation | ≤ 10% | |
| Rated current | 30 ... 20 mA | |
| Power dissipation | ≤ 800 mW including maximum output power dissipation | |
|
Entrance |
||
| Connection side | side of the field | |
| Connection | terminals 1+, 2-; 3+, 4- | |
| Nominal values | according to EN 60947-5-6 (NAMUR) | |
| Open circuit voltage/short circuit current | OK. 10 V DC current / approx. 8 mA | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
| Line fault detection | open circuit I ≤ 0.1 mA, short circuit I ≥ 6.5 mA | |
| Pulse/pause ratio | min. 100 µs/min. 100 µs | |
|
Exit |
||
| Connection side | control side | |
| Connection | terminals 5, 6; 7, 8 | |
| Nominal voltage | 30 V DC | |
| Rated current | 50 mA | |
| Response time | ≤ 200 µs | |
| Signal level |
1-signal: (external voltage) - 3 V max for 50 mA 0-signal: output blocked (off-state current ≤ 10 μA) |
|
| Exit I | signal; transistor | |
| Exit II | signal; transistor | |
| Collective error message | Power bus | |
|
Transmission characteristics |
||
| Switching frequency | ≤ 5 kHz | |
|
Galvanic isolation |
||
| Input, output | reinforced insulation according to EN 50178, rated insulation voltage 300 V, eff. | |
| Input/Power | reinforced insulation according to EN 50178, rated insulation voltage 300 V, eff. | |
| Output/Power | basic insulation according to EN 50178, rated insulation voltage 50 V eff. | |
| Exit/Exit | basic insulation according to EN 50178, rated insulation voltage 50 V eff. | |
|
Indicators/settings |
||
| Display elements | LEDs | |
| Controls | DIP switch | |
| Configuration | via DIP switches | |
| Marking | marking space at the front | |
|
Compliance with the directive |
||
| Electromagnetic compatibility |
|
|
|
|
Directive 2014/30/EU | EN 61326-1:2013 (industrial premises) |
|
Correspondence |
||
| Electromagnetic compatibility | NE 21:2011 | |
| Degree of protection | IEC 60529:2001 | |
| Protection against electric shock | IEC 61010-1:2010 | |
| Entrance | EN 60947-5-6:2000 | |
|
Environmental conditions |
||
| Ambient temperature |
-20 ... 60 °C (-4 ... 140 °F) Extended ambient temperature range up to 70°C (158°F), see manual for installation requirements |
|
|
Mechanical characteristics |
||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| weight | approx. 100 g | |
| Dimensions | 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 in) (W x H x D), case type A2 | |
| Installation | on a 35 mm DIN rail in accordance with EN 60715:2001 | |
|
Data for use in hazardous areas |
||
| EU Type Examination Certificate | BASEEFA 13 ATEX 0080 | |
|
|
Marking |
II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
|
|
|
Entrance | Ex ia |
|
|
Voltage | 10.5 V |
|
|
Current | 17.1 mA |
|
|
Power | 45 mW (linear characteristic) |
| Supply |
|
|
|
|
Maximum safe voltage | 253 V AC (Note: U m is not the nominal voltage.) |
| Exit |
|
|
|
|
Maximum safe voltage | 253 VAC (Caution: Nominal voltage may be lower.) |
| Certificate | CML 19 ATEX 4410 X | |
|
|
Marking |
II 3G Ex ec IIC T4 Gc
|
| Galvanic isolation |
|
|
|
|
Input, output | safe electrical insulation in accordance with IEC/EN 60079-11, peak voltage 375 V |
|
|
Input/Power | safe electrical insulation in accordance with IEC/EN 60079-11, peak voltage 375 V |
| Compliance with the directive |
|
|
|
|
Directive 2014/34/EU | EN IEC 60079-0:2018, EN 60079-7:2015+A1:2018, EN 60079-11:2012 |
|
International certificates |
||
| UL approval |
|
|
|
|
Control drawing | 116-0374 (cULus) |
| IECEx certification |
|
|
|
|
IECEx Certificate |
IECEx BAS 13.0046 IECEx CML 19.0147X |
|
|
IECEx marking |
[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex ec IIC T4 Gc |
II (1)G [Ex ia Ga] IIC