Technical specifications of the KFA5-DU-Ex1.D
| Main Features | ||
|---|---|---|
| Signal type | Digital input | |
|
Supply |
||
| Connection | terminals 23, 24 | |
| Nominal voltage | 115 VAC ± 10% | |
| Rated current | 35 mA | |
| Power consumption | 4 VA | |
|
Entrance |
||
| Connection side | side of the field | |
| Connection | Input I: terminals 1+, 3-; input II: terminals 13+, 14- | |
| Entrance I | according to EN 60947-5-6 (NAMUR), for electrical characteristics see manual | |
|
|
Open circuit voltage/short circuit current | 8.2 V / 10 mA |
|
|
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
|
|
Pulse duration | min. 75 µs / 1 ms see operating instructions; maximum input frequency must be observed. |
|
|
Input frequency | 0...80 Hz, pulse divider 0...1 kHz |
|
|
Line fault detection | open circuit I ≤ 0.15 mA; short circuit I > 6.5 mA |
| Entrance II | reboot | |
|
|
Active passive | I > 3 mA / I < 1.5 mA |
|
|
Open circuit voltage/short circuit current | 12 V / 3.5 mA |
|
|
Pulse duration | min. 10 ms |
|
Exit |
||
| Connection side | control side | |
| Connection | output I: terminals 10, 11, 12; output II: terminals 19+, 20- | |
| Exit I | signal, relay output | |
|
|
Contact loading | 253 VAC/ 2 A / cos φ ≥ 0.7; 40 VDC/ 2 A |
|
|
Mechanical life | 5 x 10 7 switching cycles |
|
|
On/Off Delay | OK. 20ms / approx. 20 ms |
| Exit II | signal, electronic unit, isolated | |
|
|
Contact loading | 40 V / 50 mA |
|
|
On/Off Delay | after rising input edge 3 ms; after falling input edge 2 ms |
|
|
Signal level |
1-signal: (L+) -2.5V (50mA, short circuit/overload protection) 0-signal: output blocked (off-state current ≤ 10 μA) |
|
Transmission characteristics |
||
| Entrance I |
|
|
|
|
Permission | < 0.1% of set value, min. 10 ms |
|
|
Accuracy | 2 ms |
|
|
The influence of ambient temperature | 0.003%/K (50 ppm) |
|
Galvanic isolation |
||
| Input/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff. | |
| Output I/power and reset | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff. | |
| Exit I, II against each other | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff. | |
| Output II/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff. | |
| Output II/Reset | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V eff. | |
| Reset/Power | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff. | |
|
Indicators/settings |
||
| Display elements | LEDs, display | |
| Controls | Control Panel | |
| Configuration | using the control buttons | |
| Marking | marking space at the front | |
|
Compliance with the directive |
||
| Electromagnetic compatibility |
|
|
|
|
Directive 2014/30/EU | EN 61326-1:2013 (industrial premises) |
| Low voltage |
|
|
|
|
Directive 2014/35/EU | EN 61010-1:2010 |
|
Correspondence |
||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
|
Environmental conditions |
||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
|
Mechanical characteristics |
||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| weight | approx. 300 g | |
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in) (W x H x D), case type C2 | |
| Installation | on a 35 mm DIN rail in accordance with EN 60715:2001 | |
|
Data for use in hazardous areas |
||
| EU Type Examination Certificate | TUV 99 ATEX 1408 | |
|
|
Marking |
II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
|
| Supply |
|
|
|
|
Maximum safe voltage | 253 VAC (Caution: Nominal voltage may be lower.) |
| Entrance I | terminals 1+, 3-: Ex ia | |
|
|
Voltage U o | 10.1 V |
|
|
Current I am about | 13.5 mA |
|
|
Power By _ | 34 mW (linear characteristic) |
| Entrance II | terminals 13+, 14- are not intrinsically safe | |
|
|
Maximum safe voltage U m | 40 V (Caution! Nominal voltage may be lower.) |
| Exit I | terminals 10, 11, 12 are not intrinsically safe | |
|
|
Contact loading |
253VAC/2A/cos φ>0.7; 40VDC/2A resistive load |
|
|
Maximum safe voltage | 253 V (Caution! Nominal voltage may be lower.) |
| Exit II | terminals 19+, 20- are not intrinsically safe | |
|
|
Maximum safe voltage | 40 V (Caution! Nominal voltage may be lower.) |
| Certificate | TUV 02 ATEX 1885 X | |
|
|
Marking |
II 3G Ex nA nC IIC T4 Gc
|
| Exit I |
|
|
|
|
Contact loading | 50VAC/2A/cos φ>0.7; 40VDC/2A resistive load |
| Galvanic isolation |
|
|
|
|
Input/other circuits | safe electrical insulation in accordance with IEC/EN 60079-11, peak voltage 375 V |
| Compliance with the directive |
|
|
|
|
Directive 2014/34/EU | EN 60079-0:2012+A11:2013, EN 60079-11:2012, EN 60079-15:2010 |
|
International certificates |
||
| FM approval |
|
|
|
|
Control drawing | 16-538FM-12 |
| UL approval | E223772 | |
| IECEx certification |
|
|
|
|
IECEx Certificate | IECEx TUN 03.0000 |
|
|
IECEx marking | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
II (1)G [Ex ia Ga] IIC