Technical characteristics of K-RACK.1.**.*.*.WW.01-Y*******
| Slots | ||
|---|---|---|
| Supply | Max 2, see Application section | |
| Insulators | Max 33, see Application section | |
|
Supply |
||
| Connection | power supply to the isolator via distribution panels or power bus | |
| Nominal voltage | 24 V DC, taking into account the rated voltage of the insulators used | |
| Merger | Max. 4 A, taking into account the rated voltage of the insulators used | |
| Redundancy | redundancy is possible, depending on the power supply module used | |
|
Compliance with the directive |
||
| Electromagnetic compatibility |
|
|
|
|
Directive 2014/30/EU | EN 61439-1:2011 (J.9.4.2 b), EN 61439-2:2011 |
| RoHS |
|
|
|
|
Directive 2011/65/EU (RoHS) | EN IEC 63000:2018 |
|
Environmental conditions |
||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
|
Mechanical characteristics |
||
| Connection |
|
|
|
|
Side of the field | distribution boards |
|
|
Control side | distribution boards |
|
|
Supply | cross-connect patch panels or power bus |
| Cross-section of the core |
field side: max 2.5 mm 2 control side: max 2.5 mm2 internal signal wiring: 0.25 mm 2 power supply: max 1.5 mm2 |
|
| Material |
|
|
|
|
Frame | galvanized steel |
|
|
Surface | galvanized, vibration treated |
| weight | approx. 4 kg, without modules | |
| Dimensions | 485 mm x 132 mm x 339 mm (W x H x D) | |
| Installation | slot hole 8 x 10 mm | |
| Grounding | through the front mount M8, through the side mount on both sides M5 | |