Technical data KFD0-CS-Ex2.52
| Main Features | ||
|---|---|---|
| Signal type | Analog input | |
|
Supply |
||
| Nominal voltage | 4...24 VDC, loop powered | |
| Power dissipation | 150 mW | |
| Power consumption | 1 W | |
|
Control chain |
||
| Connection | terminals 12-, 11+; 8-, 10-, 9+ | |
| Voltage | 4 ... 24 V DC for 4 V < U in < 24 V: 0.97 x U in - (85 x current in A) - 1.3 | |
| Current | 4 ... 20 mA | |
|
Excitation circuit |
||
| Connection | terminals 1+, 2-; 4+, 5- | |
| Transmission range |
current: 4 ... 24 mA voltage: 4 ... 24 V DC |
|
|
Transmission characteristics |
||
| Accuracy | 0.1% | |
| Deviation |
|
|
|
|
After calibration |
±20 µA incl. calibration, linearity, hysteresis, and load variations at 20 °C (68 °F), U in ≤ 20 V +20 µA/-50 µA incl. calibration, linearity, hysteresis, and load variations at 20 °C (68 °F), 20 V < U in < 24 V |
|
|
The influence of ambient temperature |
± 1 µA/K (0 ... 50 °C (32 ... 122 °F)), U in ≤ 12 V ± 2 µA/K (0 ... 60 °C (32 ... 140 °F)), Uin ≤ 18 V ± 5 µA/K (-20 ... 60 °C (-4 ... 140 °F)), Uin ≤ 24 V |
| Rise time | ≤ 10 ms at 4 ... 20 mA and 250 Ohm load | |
|
Galvanic isolation |
||
| Input, output | safe electrical insulation in accordance with IEC/EN 60079-11, peak voltage 375 V | |
|
Indicators/settings |
||
| Marking | marking space at the front | |
|
Compliance with the directive |
||
| Electromagnetic compatibility |
|
|
|
|
Directive 2014/30/EU | EN 61326-1:2013 (industrial premises) |
|
Correspondence |
||
| Electromagnetic compatibility | NE 21:2011 | |
| Degree of protection | IEC 60529:2001 | |
| Protection against electric shock | UL 61010-1:2012 | |
|
Environmental conditions |
||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
|
Mechanical characteristics |
||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| weight | approx. 100 g | |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) (W x H x D), case type B2 | |
| Installation | on a 35 mm DIN rail in accordance with EN 60715:2001 | |
|
Data for use in hazardous areas |
||
| EU Type Examination Certificate | BASEEFA 03 ATEX 0141 | |
|
|
Marking |
II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C ≤ T ambient ≤ 60 °C), [circuit(s ) in zone 0/1/2]
|
|
|
Voltage | 25.2 VDC |
|
|
Current | 0 mA |
| Exit |
|
|
|
|
Maximum safe voltage | 253 V rms (Note: Nominal voltage may be lower.) |
| Certificate | TUV 99 ATEX 1499 X | |
|
|
Marking |
II 3G Ex nA II T4 [device in zone 2]
|
| Galvanic isolation |
|
|
|
|
Input, output | safe electrical insulation in accordance with IEC/EN 60079-11, peak voltage 375 V |
| Compliance with the directive |
|
|
|
|
Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020, EN 60079-11:2012, EN 60079-15:2010 |
|
International certificates |
||
| FM approval |
|
|
|
|
Control drawing | 116-0129 |
| UL approval |
|
|
|
|
Control drawing | 116-0173 (cULus) |
| IECEx certification |
|
|
|
|
IECEx Certificate | IECEx BAS 08.0059 |
|
|
IECEx marking | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C ≤ T ambient ≤ 60 °C), [circuit(s ) in zone 0/1/2]