Technical specifications of the KFD2-VR-Ex1.18
| Main Features | ||
|---|---|---|
| Signal type | Analog input | |
|
Supply |
||
| Connection | Power bus or terminals 11+, 12- | |
| Nominal voltage | 20 ... 35 V DC | |
| pulsation | within delivery tolerances | |
| Rated current | < 20 mA | |
|
Entrance |
||
| Connection side | side of the field | |
| Connection | terminals 4+, 5- | |
| Input impedance | min. 10 MOhm | |
| Transmission range | 0 ... 12 V | |
| Voltage/current offset | < 2 mV / < 7 nA | |
|
Exit |
||
| Connection side | control side | |
| Connection | terminals 7-, 8+ | |
| Voltage | 0 ... 12 V | |
| Output impedance | Max 20 Ohm | |
|
Transmission characteristics |
||
| Cutoff frequency | 1.2 kHz (-3 dB) | |
| Deviation |
|
|
|
|
After calibration | ± 5 mV at 20 °C (68 °F) |
|
|
The influence of ambient temperature | ≤ 0.005% of span per K |
| Rise time | ≤ 0.4 ms | |
|
Galvanic isolation |
||
| Output/Power | functional insulation, rated insulation voltage 50 V AC | |
|
Indicators/settings |
||
| Display elements | LED | |
| Marking | marking space at the front | |
|
Compliance with the directive |
||
| Electromagnetic compatibility |
|
|
|
|
Directive 2014/30/EU | EN 61326-1:2013 (industrial premises) |
|
Correspondence |
||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
|
Environmental conditions |
||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
|
Mechanical characteristics |
||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| weight | approx. 100 g | |
| Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 in) (W x H x D), case type B1 | |
| Installation | on a 35 mm DIN rail in accordance with EN 60715:2001 | |
|
Data for use in hazardous areas |
||
| EU Type Examination Certificate | BAS 01 ATEX 7262 | |
|
|
Marking |
II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C ≤ T ambient ≤ 60 °C), [circuit(s ) in zone 0/1/2]
|
|
|
Voltage | 18 B |
|
|
Current | 4.2 mA |
|
|
Power | 19 MW |
| Supply |
|
|
|
|
Maximum safe voltage | 250 V (Caution! Nominal voltage is lower.) |
| Exit |
|
|
|
|
Maximum safe voltage | 250 V (Caution! Nominal voltage is lower.) |
| Certificate | BASEEFA 10 ATEX 0079X | |
|
|
Marking |
II 3G Ex ec IIC T4 Gc [device in zone 2]
|
| Galvanic isolation |
|
|
|
|
Input, output | safe electrical insulation in accordance with IEC/EN 60079-11, peak voltage 375 V |
|
|
Input/Power | safe electrical insulation in accordance with IEC/EN 60079-11, peak voltage 375 V |
| Compliance with the directive |
|
|
|
|
Directive 2014/34/EU | EN 60079-0:2012+A11:2013, EN 60079-11:2012, EN 60079-7:2015+A1:2018 |
|
International certificates |
||
| FM approval |
|
|
|
|
Control drawing | 116-0129 |
| UL approval |
|
|
|
|
Control drawing | 116-0173 (cULus) |
| CSA approval |
|
|
|
|
Control drawing | 116-0132 |
| IECEx certification |
|
|
|
|
IECEx Certificate | IECEx BAS 10.0040X |
|
|
IECEx marking | Ex ec IIC T4 Gc |
II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C ≤ T ambient ≤ 60 °C), [circuit(s ) in zone 0/1/2]