Technical characteristics of the KFD0-TR-Ex1
| Main Features | ||
|---|---|---|
| Signal type | Analog input | |
|
Supply |
||
| Nominal voltage | 12...35 VDC loop powered | |
| Power dissipation | 0.4 W | |
|
Entrance |
||
| Connection side | side of the field | |
| Connection | terminals 1, 2-, 3+ are suitable for Pt100, 2- and 3-wire connection | |
| Lead resistance | Max 100 Ohm per line | |
| Current measurement | approx. 1 mA | |
|
Exit |
||
| Connection side | control side | |
| Connection | terminals 9+, 8- | |
| Load | (U-12 V) / 0.02 A | |
| Current output | 4 ... 20 mA, limited ≤ 35 mA | |
| Malfunction signal | scaling ≥ 22 mA (limited to 35 mA) | |
|
Transmission characteristics |
||
| Measurement range |
range without linearization 25 ... 800 °C (77 ... 1472 °F)/with linearization 25 ... 375 °C (77 ... 707 °F), both with adjustable zero point without linearization -200 ... 400 °C (-328 ... 752 °F)/with linearization -30 ... 375 °C (-22 ... 707 °F), both adjustable |
|
| Deviation |
|
|
|
|
After calibration | 0.1% of full scale including linearity and hysteresis |
|
|
The influence of ambient temperature | span and zero point 0.015%/K or ±10 mOhm/K |
|
|
Influence of supply voltage | 6.5 ppm/V |
| Rise time | 250 ms | |
|
Galvanic isolation |
||
| Input, output | accessible | |
|
Indicators/settings |
||
| Controls |
DIP switch rotary switch |
|
| Configuration |
using DIP switches using the rotary switch |
|
| Marking | marking space at the front | |
|
Compliance with the directive |
||
| Electromagnetic compatibility |
|
|
|
|
Directive 2014/30/EU | EN 61326-1:2013 (industrial premises) |
|
Correspondence |
||
| Isolation Coordination | EN 50178 | |
| Galvanic isolation | EN 50178 | |
| Degree of protection | IEC 60529 | |
|
Environmental conditions |
||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
|
Mechanical characteristics |
||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| weight | approx. 150 g | |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) (W x H x D), case type B2 | |
| Installation | on a 35 mm DIN rail in accordance with EN 60715:2001 | |
|
Data for use in hazardous areas |
||
| EU Type Examination Certificate | ZELM 00 ATEX 0036 | |
|
|
Marking |
II (1)GD [EEx ia] IIC
|
|
|
Voltage | 16.1 V |
|
|
Current | 33 mA |
|
|
Power | 131 MW |
| Certificate | TUV 01 ATEX 1777 X | |
|
|
Marking |
II 3G Ex nA II T4
|
| Galvanic isolation |
|
|
|
|
Input, output | safe electrical insulation in accordance with IEC/EN 60079-11, peak voltage 375 V |
| Compliance with the directive |
|
|
|
|
Directive 2014/34/EU | EN 60079-0:2018+AC:2020, EN 60079-11:2012, EN 60079-15:2010 |
|
International certificates |
||
| CSA approval | 1029981 | |
|
|
Control drawing | 116-0132 |
| IECEx certification |
|
|
|
|
IECEx Certificate | IECEx TUN 06.0004 |
|
|
IECEx marking | [Zone 0] [Ex ia] IIC |
II (1)GD [EEx ia] IIC