Technical data EI-0D2-10Y-10B-LT
| Product Description |
|---|
| Ethernet isolator with a temperature range of -20 °C ... +55 °C |
|
Supply |
||
|---|---|---|
| Nominal voltage | 19.2...35 VDC | |
| Rated current | 150...100 mA | |
| Power dissipation | 3 W | |
|
Ethernet interface |
||
| Intrinsically safe port | 10 BASE-T/100 BASE-TX | |
| Non-intrinsically safe port | 10 BASE-T/100 BASE-TX | |
| Connection type | 2 RJ-45 connectors, IEC 60603-7 | |
| Connector pinout | connector; EIA/TIA 568 B | |
| Transfer speed | 10/100 Mbps, auto-negotiation | |
| Working mode | half/full duplex | |
| Cable type | CAT5e S/FTP AWG 24, installation cable, left/right ratio max 10 µH/Ohm for all wire combinations | |
| Length of intrinsically safe cable | type 100 m/20 °C | |
| Total cable length | type 200 m/20 °C | |
| Number of insulators | Max 2 serial connection | |
|
Indicators/controls |
||
| Power LED indicator | green: power on | |
| LED ACT | yellow: connection is active | |
| LED 10/100 | Yellow ON: 100 Mbps transfer rate, OFF: 10 Mbps | |
|
Compliance with directives |
||
| Electromagnetic compatibility |
|
|
|
|
Directive 2014/30/EU | EN 61326-1:2013 |
|
Standard compliance |
||
| Galvanic isolation | EN 50020 | |
| Degree of protection | IEC 60529 | |
| Climate conditions | DIN IEC 721 | |
| Impact resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Ethernet | IEEE 802.3, IEEE 802.3u | |
|
Environmental conditions |
||
| Ambient temperature | -20...55°С (-4...131°F) | |
| Storage temperature | -40...85°С (-40...185°F) | |
| Relative humidity | ≤ 95% non-condensing | |
| Impact resistance | 15 g 11 ms | |
| Vibration resistance | 1 g 10...150 Hz | |
| Degree of pollution | Max. 2, according to IEC 60664 | |
|
Mechanical characteristics |
||
| Connection type | Terminals | |
| Cross-section of the core | up to 2.5 mm 2 | |
| Body material | Polyamide PA 66 | |
| Degree of protection | IP20 according to EN 60529 | |
| Weight | 195 g | |
| Installation | DIN rail mounting | |
|
Data for use in hazardous areas |
||
| EC Type Examination Certificate | PTB 07 ATEX 2025 X | |
|
|
Marking |
II (1) G [Ex ia Ga] IIB , II (1) D [Ex ia Da] IIIC , II 3(1)G Ex nA [ia Ga] IIB T4 Gc II 3 (1D) G Ex nA [ia IIIC Da] IIB T4 Gc I (M1) [Ex ia Ma] I
|
| Supply |
|
|
|
|
Maximum safe voltage | 253 V AC |
| Compliance with directives |
|
|
|
|
Directive 2014/34/EU | EN 60079-0:2012, EN 60079-11:2012, EN 60079-15:2010 |
|
International approvals |
||
| CSA approval | CSA 15.70016295 | |
|
|
Control drawing | 116-B032 |
|
|
Approved for | Class I, Zone 2, AEx/Ex nA [ia Ga] IIB T4 Gc Class I, Zone 2, AEx/Ex nA [ia Da IIIC] IIB T4 Gc |
| IECEx approval | IECEx PTB 09.0053X | |
|
|
Approved for |
[Ex ia Ga] IIB [Ex ia Da] IIIC Ex nA [ia Ga] IIB T4 Gc Ex nA [ia IIIC Da] IIB T4 Gc [Ex ia Ma] I |
|
Certificates and approvals |
||
| Patents | This product may be covered by the following patent: US7,687,791. | |
II (1) G [Ex ia Ga] IIB ,