Technical data of the HiATB01-HART-4X8-Y1
| Product Description |
|---|
| HART communication board |
|
Supply |
||
|---|---|---|
| Connection | X20: terminals 1, 3 (+); 2, 4 (-) | |
| Nominal voltage | 24VDC SELV/PELV | |
| Voltage drop | 0.9V, voltage drop across the series diode on the terminal board must be taken into account. | |
| Pulsation | ≤ 10% | |
| Merger | 0.5 A | |
| Power dissipation | ≤ 500 mW, without modules | |
| Reverse polarity protection | Yes | |
|
Interface |
||
| Type/number | 2 x RS-485 | |
|
Reservation |
||
| Supply | Redundancy is possible. Power is switched off, monitored, and protected by fuses. | |
|
Indicators/settings |
||
| Display elements |
LED PWR1 (terminal panel power supply), green LED LED PWR2 (terminal panel power supply), green LED |
|
|
Compliance with directives |
||
| Electromagnetic compatibility |
|
|
|
|
Directive 2014/30/EU | EN 61326-1:2013 (industrial premises) |
|
Correspondence |
||
| Electromagnetic compatibility |
NE 21:2012 For more information, please see the system description. |
|
| Degree of protection | IEC 60529:2001 | |
|
Environmental conditions |
||
| Ambient temperature | -20...60°С (-4...140°F) | |
| Storage temperature | -40...70°С (-40...158°F) | |
|
Mechanical characteristics |
||
| Degree of protection | IP20 | |
| Connection |
|
|
|
|
Control side |
RS-485: 1 screw terminal, black. HART: 4 IDC connectors, 34-pin. |
|
|
Supply | removable screw terminals, black |
| Cross-section of the core | screw terminals: 0.25...1.5 mm2 (24...12 AWG) | |
| Material | body: polycarbonate, 10% glass fiber reinforced | |
| Weight | approx. 210 g | |
| Dimensions | 50 x 200 x 163 mm (1.97 x 7.9 x 6.42 in) (W x H x D) depth including module assembly | |
| Installation | on a 35 mm DIN mounting rail in accordance with EN 60715:2001 | |