Technical data FI-PFH-NS0137-R
| HART signal channels (non-intrinsically safe) | ||
|---|---|---|
| Load resistor | 220 Ohm, turns on | |
| Interface | ||
| Type | Multiplexer connection: IDC plug, 26-pin | |
| Signal lines | ||
| Rated current | Max. 30 mA per channel | |
| Indicators/settings | ||
| Controls |
DIP switch |
|
| DIP switch |
select operating mode: - ON: without load resistor - OFF: with load resistor |
|
| Factory setting | DIP switches S1 and S2: ON. | |
| Compliance with directives | ||
| Electromagnetic compatibility |
|
|
|
|
Directive 2014/30/EU | EN 61326-1:2013 (industrial premises) |
| Correspondence | ||
| Electromagnetic compatibility |
NE 21:2017 For more information, please see the system description. |
|
| Degree of protection | IEC 60529:2001 | |
| Impact resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Environmental conditions | ||
| Ambient temperature | 0...50°С (32...122°F) | |
| Storage temperature | -15...50°С (5...122°F) | |
| Relative humidity | ≤ 93% non-condensing | |
| Impact resistance | 15 g, 11 ms | |
| Vibration resistance | 1 g, 10...150 Hz | |
| Mechanical characteristics | ||
| Degree of protection | IP20 | |
| Connection |
|
|
|
|
Field side | screw terminals, green |
|
|
Control side |
screw terminals, green HART: 1 IDC plug, 26-pin |
| Cross-section of the core | 0.25...1.5 mm2 ( 24...16 AWG) | |
| Material |
|
|
|
|
Frame | PVC |
| Weight | approx. 210 g | |
| Dimensions | 110 x 125 x 61 mm (4.3 x 4.9 x 2.4 in) (W x H x D) | |
| Installation | on a 35 mm DIN mounting rail in accordance with EN 60715:2001 | |
| Data for use in hazardous areas | ||
| Certificate | PF 11 CERT 1930 X | |
|
|
Marking |
II 3G Ex nA IIC T4 Gc
|
| Compliance with directives |
|
|
|
|
Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020, EN 60079-15:2010 |
II 3G Ex nA IIC T4 Gc