Technical data of KFD2-CRG2-1.D
| Main Features | ||
|---|---|---|
| Signal type | Analog input | |
|
Parameters related to functional safety |
||
| Safety Integrity Level (SIL) | SIL 2 | |
|
Supply |
||
| Connection | Power bus or terminals 23+, 24- | |
| Nominal voltage | 20...30 V DC | |
| Rated current | approx. 130 mA | |
| Power dissipation | 2 W | |
| Power consumption | 2.5 W | |
|
Interface |
||
| Programming interface | programming connector | |
|
Entrance |
||
| Connection side | side of the field | |
| Connection | terminals 1, 2, 3 | |
| Entrance I |
|
|
|
|
Input signal | 0/4...20 mA |
|
|
Available voltage | ≥ 15 V at 20 mA |
|
|
Open circuit voltage/short circuit current | 24 V/33 mA |
|
|
Input impedance | 45 Ohm (terminals 2, 3) |
|
|
Line fault detection | open circuit I < 0.2 mA; short circuit I > 22 mA |
|
Exit |
||
| Connection side | control side | |
| Connection |
output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 Output: analog terminals 8+, 7- |
|
| Output signal | 0...20 mA or 4...20 mA | |
| Exit I, II | signal, relay | |
|
|
Contact loading | 250 V AC / 2 A / cos φ ≥ 0.7; 40 V DC / 2 A |
|
|
Mechanical life | 5 x 10 7 switching cycles |
| Result III | Analog signal | |
|
|
Current range | 0...20 mA or 4...20 mA |
|
|
Open circuit voltage | Max 24V DC |
|
|
Load | Max. 650 Ohm |
|
|
Malfunction signal | lower limit I ≤ 3.6 mA, upper limit I ≥ 21.5 mA (according to NAMUR NE43) |
| On/Off Delay | 0...250 s, adjustable | |
|
Transfer characteristics |
||
| Entrance I |
|
|
|
|
Accuracy | < 30 μA |
|
|
The influence of ambient temperature | 0.003%/K (30 ppm) |
| Exit I, II |
|
|
|
|
Delayed response | ≤ 200 ms when jumping from 0 to 20 mA |
| Result III |
|
|
|
|
Permission | ≤ 10 μA |
|
|
Accuracy | < 20 μA |
|
|
The influence of ambient temperature | 0.005%/K (50 ppm) |
|
|
Reaction time | < 650 ms jump from 0 to 20 mA input, 90% of full scale output |
|
Galvanic isolation |
||
| Input/Other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff. | |
| Output I, II/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff. | |
| Mutual output I, II, III | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff. | |
| Output III/Power and General Error | Functional insulation according to IEC 62103, rated insulation voltage 50 V eff. | |
| Interface/Power Supply and General Error | Functional insulation according to IEC 62103, rated insulation voltage 50 V eff. | |
|
Indicators/settings |
||
| Display elements | LEDs, display | |
| Controls | Control Panel | |
| Configuration |
using the control buttons via PACTware |
|
| Marking | marking space at the front | |
|
Compliance with the directive |
||
| Electromagnetic compatibility |
|
|
|
|
Directive 2014/30/EU | EN 61326-1:2013 (industrial premises) |
| Low voltage |
|
|
|
|
Directive 2014/35/EU | EN 61010-1:2010 |
|
Correspondence |
||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
|
Environmental conditions |
||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
|
Mechanical characteristics |
||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| weight | 300 g | |
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in) (W x H x D), case type C2 | |
| Installation | on a 35 mm DIN mounting rail in accordance with EN 60715:2001 | |
|
International approvals |
||
| UL approval | E223772 | |