Technical specifications of the KFD2-SR3-2.2S
| Main Features | ||
|---|---|---|
| Signal type | Digital input | |
|
Parameters related to functional safety |
||
| Safety Integrity Level (SIL) | SIL 2 | |
|
Supply |
||
| Connection | Power bus or terminals 14+, 15- | |
| Nominal voltage | 19 ... 30 V DC current | |
| pulsation | ≤ 10% | |
| Rated current | 30 ... 20 mA | |
| Power consumption | < 600 mW | |
|
Entrance |
||
| Connection side | side of the field | |
| Connection | terminals 1+, 2+, 3-; 4+, 5+, 6- | |
| Nominal values | according to EN 60947-5-6 (NAMUR) | |
| Open circuit voltage/short circuit current | OK. 10 V DC current / approx. 8 mA | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
| Line fault detection | open circuit I ≤ 0.1 mA, short circuit I ≥ 6.5 mA | |
| Pulse/pause ratio | min. 20 ms/min. 20 ms | |
|
Exit |
||
| Connection side | control side | |
| Connection | output I: terminals 7, 8; output II: terminals 8, 9; output III: terminals 10, 11; output IV: terminals 11, 12 | |
| Exit I, II, III, IV | channel 1, 2; relay | |
| Contact loading | 48 VAC/1 A/cos φ > 0.7; 40 VDC/1 A resistive load | |
| Minimum switching current | 1 mA / 24 V DC current | |
| On/Off Delay | OK. 20ms / approx. 20 ms | |
| Mechanical life | 10 8 switching cycles | |
| Collective error message | Power bus | |
|
Transmission characteristics |
||
| Switching frequency | ≤ 10 Hz | |
|
Galvanic isolation |
||
| Input, output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff. | |
| Input/Power | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff. | |
| Output/Power | Basic insulation according to IEC/EN 61010-1, rated insulation voltage 32 V eff. , functional insulation, rated insulation voltage 50 V eff. | |
| Exit/Exit | Basic insulation according to IEC/EN 61010-1, rated insulation voltage 32 V eff. , functional insulation, rated insulation voltage 50 V eff. | |
|
Indicators/settings |
||
| Display elements | LEDs | |
| Controls | DIP switch | |
| Configuration | via DIP switches | |
| Marking | marking space at the front | |
|
Compliance with the directive |
||
| Electromagnetic compatibility |
|
|
|
|
Directive 2014/30/EU | EN 61326-1:2013 (industrial premises) |
|
Correspondence |
||
| Electromagnetic compatibility | NE 21:2012, EN 61326-3-2:2008 | |
| Degree of protection | IEC 60529:2001 | |
| Entrance | EN 60947-5-6:2000 | |
|
Environmental conditions |
||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
|
Mechanical characteristics |
||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| weight | approx. 150 g | |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) (W x H x D), case type B2 | |
| Installation | on a 35 mm DIN rail in accordance with EN 60715:2001 | |
|
Data for use in hazardous areas |
||
| Certificate | PF 16 CERT 3903 X | |
|
|
Marking |
II 3G Ex nA nC IIC T4 Gc
|
| Compliance with the directive |
|
|
|
|
Directive 2014/34/EU | EN 60079-0:2012+A11:2013, EN 60079-15:2010 |
|
International certificates |
||
| UL approval | E106378 | |
| IECEx certification |
|
|
|
|
IECEx Certificate | IECEx EXA 16.0001X |
|
|
IECEx marking | Ex nA nC IIC T4 Gc |
II 3G Ex nA nC IIC T4 Gc