Technical data KFD0-CC-1
| Main Features | ||
|---|---|---|
| Signal type | Analog input | |
| Supply | ||
| Nominal voltage | 12...35 VDC loop powered | |
| Power dissipation | 0.4 W | |
| Entrance | ||
| Connection side | side of the field | |
| Connection | terminals 1+, 2- | |
| Current range | 0...20 mA, load ≤ 50 Ohm | |
| Voltage range | 0...10 V, load ≥ 100 kOhm | |
| Exit | ||
| Connection side | control side | |
| Connection | terminals 9+, 8- | |
| Load | (U -12 V)/0.02 A | |
| Current output | 4...20 mA, limited to ≤ 35 mA | |
| Malfunction signal | downscaling ≤ 3 mA | |
| Transfer characteristics | ||
| Deviation |
|
|
|
|
After calibration | 0.1% of full scale |
|
|
Temperature effect | range: 0.050% of range /K; zero point: 0.060% of range /K |
|
|
Linearization | ≤ 0.04% of full scale |
|
|
Influence of supply voltage | 6.5 ppm/V |
| Rise time | 250 ms | |
| Galvanic isolation | ||
| Input, output | safe insulation according to EN 50178, rated insulation voltage 253 V eff. | |
| Indicators/settings | ||
| Controls |
DIP switch potentiometer |
|
| Configuration |
via DIP switches via a potentiometer |
|
| Marking | marking space at the front | |
| Compliance with directives | ||
| Electromagnetic compatibility |
|
|
|
|
Directive 2014/30/EU | EN 61326-1:2013 (industrial premises) |
| Correspondence | ||
| Isolation Coordination | EN 50178 | |
| Galvanic isolation | EN 50178 | |
| Degree of protection | IEC 60529 | |
| Environmental conditions | ||
| Ambient temperature | -20...70°С (-4...158°F) | |
| Mechanical characteristics | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Weight | approx. 100 g | |
| Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 in) (W x H x D), case type B1 | |
| Installation | on a 35 mm DIN mounting rail in accordance with EN 60715:2001 | |