Technical characteristics of the KFD2-DWB-1.D
| Main Features | ||
|---|---|---|
| Signal type | Digital input | |
|
Parameters related to functional safety |
||
| Safety Integrity Level (SIL) | SIL 2 | |
|
Supply |
||
| Connection | terminals 23+, 24- or power module/power bus | |
| Nominal voltage | 20 ... 30 V DC | |
| Rated current | approx. 100 mA | |
| Power dissipation/power consumption | ≤ 1.8 W / 1.8 W | |
|
Entrance |
||
| Connection side | side of the field | |
| Connection |
Input I: 2-wire sensor: terminals 1+, 3- 3-wire sensor: terminals 1+, 2- and 3 Input II: terminals 13+, 14- start blocking; |
|
| Entrance I | 2- or 3-wire sensor, sensor according to EN 60947-5-6 (NAMUR) or mechanical contact | |
|
|
Open circuit voltage/short circuit current | 22 V / 40 mA |
|
|
Input impedance | 4.7 kOhm |
|
|
Switching point/switching hysteresis | logical 1: > 2.5 mA; logical 0: < 1.9 mA |
|
|
Pulse duration | > 50 µs |
|
|
Input frequency | 0.001...12000 Hz |
|
|
Line fault detection | open circuit I ≤ 0.15 mA; short circuit I > 4 mA |
| Entrance II | Start-up lock: 1...1000 sec, adjustable in 1 sec increments | |
|
|
Active passive | I > 4 mA (min. 100 ms) / I < 1.5 mA |
|
|
Open circuit voltage/short circuit current | 18 V / 5 mA |
|
Exit |
||
| Connection side | control side | |
| Connection |
output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 |
|
| Exit I, II | signal, relay | |
|
|
Contact loading | 250 V AC / 2 A / cos φ ≥ 0.7; 40 V DC / 2 A |
|
|
Mechanical life | 5 x 10 7 switching cycles |
|
|
On/Off Delay | OK. 20ms / approx. 20 ms |
| Collective error message | Power bus | |
|
Transmission characteristics |
||
| Entrance I |
|
|
|
|
Measurement range | 0.001...12000 Hz |
|
|
Permission | 0.1% of the measured value, ≥ 0.001 Hz |
|
|
Accuracy | 0.1% of the measured value, > 0.001 Hz |
|
|
Measuring time | < 100 ms |
|
|
The influence of ambient temperature | 0.003%/K (30 ppm) |
| Exit I, II |
|
|
|
|
Delayed response | ≤ 200 ms |
|
Galvanic isolation |
||
| Input/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff. | |
| Exit I, II against each other | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff. | |
| Output I, II/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff. | |
| Launch/Power Correction and Collective Error | Functional insulation according to IEC 62103, rated insulation voltage 50 V, eff. | |
|
Indicators/settings |
||
| Display elements | LEDs, display | |
| Controls | Control Panel | |
| Configuration | using the control buttons | |
| Marking | marking space at the front | |
|
Compliance with the directive |
||
| Electromagnetic compatibility |
|
|
|
|
Directive 2014/30/EU | EN 61326-1:2013 (industrial premises) |
| Low voltage |
|
|
|
|
Directive 2014/35/EU | EN 61010-1:2010 |
|
Correspondence |
||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
|
Environmental conditions |
||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
|
Mechanical characteristics |
||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| weight | 300 g | |
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in) (W x H x D), case type C2 | |
| Installation | on a 35 mm DIN rail in accordance with EN 60715:2001 | |
|
Data for use in hazardous areas |
||
| Certificate | PF 08 CERT 1216 X | |
|
|
Marking |
II 3G Ex nA nC IIC T4 Gc
|
| Exit I, II |
|
|
|
|
Contact loading | 50VAC/2A/cos φ>0.7; 40VDC/1A resistive load |
| Environmental conditions |
|
|
|
|
Ambient temperature | -20 ... 50 °C (-4 ... 122 °F) |
| Compliance with the directive |
|
|
|
|
Directive 2014/34/EU | EN 60079-0:2012+A11:2013, EN 60079-15:2010 |
|
International certificates |
||
| UL approval | E223772 | |
II 3G Ex nA nC IIC T4 Gc