Technical data S1SD-1FI-1R
| Main Features | ||
|---|---|---|
| Signal type | Digital input | |
| Supply | ||
| Connection | Power bus or terminals 1-, 2+ | |
| Nominal voltage | 16.8...31.2 VDC | |
| Power dissipation | 0.6 W | |
| Power consumption | 1.1 W | |
| Interface | ||
| Programming interface | programming connector | |
| Entrance | ||
| Connection side | side of the field | |
| NAMUR sensor |
|
|
|
|
Type | 2-wire |
|
|
Connection | terminals 5+, 6 |
|
|
Signal | according to EN 60947-5-6 (NAMUR) |
|
|
Power supply for sensors | 8 V |
|
|
Open circuit | < 0.1 mA |
|
|
Switching point | 1.2...2.1 mA |
|
|
Short circuit | > 6 mA |
|
|
Input impedance | 1 kOhm |
| Mechanical contact |
|
|
|
|
Type | 2-wire |
|
|
Connection | terminals 5+, 6 |
|
|
Power supply for sensors | 15 V |
|
|
External power supply | ≤ 32 V |
|
|
Switching point | 8...10 V/1.2...2.1 mA |
|
|
Frequency | 0...50 Hz, debounce filter |
|
|
Input impedance | 4 kOhm |
| CH sensor |
|
|
|
|
Type | 2-wire |
|
|
Connection | terminals 5+, 6 |
|
|
Power supply for sensors | 8 V |
|
|
Open circuit | < 0.1 mA |
|
|
Switching point | 1.2...2.1 mA |
|
|
Short circuit | > 6 mA |
|
|
Input impedance | 1 kOhm |
| 2-wire DC current sensor |
|
|
|
|
Type | 2-wire |
|
|
Connection | terminals 5+, 6 |
|
|
Signal | according to EN 60947-5-2 |
|
|
Power supply for sensors | 16V/25mA, short circuit protection |
|
|
External power supply | ≤ 32 V |
|
|
Switching point | 2...5 mA |
|
|
Input impedance | 1 kOhm |
| S0 sensor |
|
|
|
|
Type | 2-wire |
|
|
Connection | terminals 5+, 6 |
|
|
Signal | according to EN 62053-31, type B |
|
|
Power supply for sensors | 15 V |
|
|
Switching point | 0.15...2 mA |
|
|
Input impedance | 4 kOhm |
| NPN sensor |
|
|
|
|
Type | 3-wire |
|
|
Connection | terminals 5+, 6, 7- |
|
|
Signal | according to EN 60947-5-2 |
|
|
Power supply for sensors | 16V/25mA, short circuit protection |
|
|
External power supply | ≤ 32 V |
|
|
Switching point | 3...5 V |
|
|
Input impedance | 4 kOhm |
| PNP sensor |
|
|
|
|
Type | 3-wire |
|
|
Connection | terminals 5+, 6, 7- |
|
|
Signal | according to EN 60947-5-2 |
|
|
Power supply for sensors | 16V/25mA, short circuit protection |
|
|
External power supply | ≤ 32 V |
|
|
Switching point | 8...10 V |
|
|
Input impedance | 4 kOhm |
| AC/DC voltage source |
|
|
|
|
Connection | terminals 6, 7- |
|
|
Signal | Max ±30 V |
|
|
Switching point | 150...400 mV |
|
|
Input impedance | 4 kOhm |
| Functional input |
|
|
|
|
Connection | Terminal 8 |
|
|
Open circuit voltage | 7.5 V |
|
|
Input impedance | approx. 50 kOhm |
|
|
Function 1 | activation startup override |
|
|
Switching point | < 3 V, edge triggered |
|
|
Adjustment range | 1...6500 s |
|
|
Function 2 | reset restart prohibition |
|
|
Switching point | > 12 V, edge triggered |
| Exit | ||
| Connection side | control side | |
| Connection | terminals 3, 4: | |
| Exit | signal, relay | |
| Contact loading | 253VAC/2A/cos φ>0.7; 126.5VAC/4A/cos φ>0.7; 30VDC/2A resistive load | |
| Minimum switching current | 2 mA / 24 VDC | |
| On/Off Delay | ≤ 20 ms / ≤ 20 ms | |
| Mechanical life | 10 7 switching cycles | |
| Transfer characteristics | ||
| Accuracy | Max. 0.1% of measurement value | |
| Measurement time | ≤ 100 ms | |
| The influence of ambient temperature | < 100 ppm/K of measured value | |
| Frequency range | 0.01...50000 Hz | |
| Galvanic isolation | ||
| Output/power supply | Safe electrical insulation due to reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V, rms test voltage 3 kV, 50 Hz, 1 min. | |
| Input/Other circuits | Safe electrical insulation due to reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V, rms test voltage 3 kV, 50 Hz, 1 min. | |
| Indicators/settings | ||
| Display elements | LEDs | |
| Controls | DIP switch | |
| Configuration |
via DIP switches via software |
|
| Marking | marking space at the front | |
| Compliance with directives | ||
| Electromagnetic compatibility |
|
|
|
|
Directive 2014/30/EU | EN 61326-1:2013 (industrial premises) |
| Low voltage |
|
|
|
|
Directive 2014/35/EU | EN 61010-1:2010 |
| Correspondence | ||
| Degree of protection | IEC 60529:2001 | |
| Protection against electric shock | EN 61010-1:2010 | |
| Environmental conditions | ||
| Ambient temperature | -25...70°С (-13...158°F) | |
| Storage temperature | -40...85°С (-40...185°F) | |
| Damaging gas | Designed for use in environmental conditions in accordance with ISA-S71.04-1985, severity level G3 | |
| Mechanical characteristics | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Cross-section of the core | 0.5...2.5 mm2 ( 20...14 AWG) | |
| Weight | approx. 60 g | |
| Dimensions | 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 in) (W x H x D), housing type S1 | |
| Installation | on a 35 mm DIN mounting rail in accordance with EN 60715:2001 | |