Technical data of the S1SD-1AI-1R
| Main Features | ||
|---|---|---|
| Signal type | Analog input | |
| Supply | ||
| Connection | Power bus or terminals 1-, 2+ | |
| Nominal voltage | 16.8...31.2 VDC | |
| Power dissipation | 0.6 W | |
| Power consumption | 0.8 W | |
| Interface | ||
| Programming interface | programming connector | |
| Entrance | ||
| Connection side | side of the field | |
| Transmission range |
Linearity range: unipolar -1...110% bipolar -110...110% |
|
| Entrance I |
|
|
|
|
Connection | terminals 5, 6, 7- |
|
|
Input signal | 0/4...20 mA, 0/2...10 mA, ± 10 mA, ± 20 mA, max. 50 mA |
|
|
Input impedance | ≤ 25 Ohm |
| Entrance II |
|
|
|
|
Connection | terminals 7-, 8+ |
|
|
Input signal | 0/1...5 V, 0/2...10 V, ±5 V, ±10 V, max 30 V |
|
|
Input impedance | > 1 MOhm |
| Entrance III |
|
|
|
|
Connection | terminals 5+, 6- |
|
|
Input signal | 0/4...20 mA |
|
|
Available voltage | 16 V at 20 mA |
|
|
Open circuit voltage/short circuit current | ≤ 22 V/30 mA |
| Entrance IV |
|
|
|
|
Connection | terminals 5, 7 |
|
|
Input type | reset restart prohibition |
| Exit | ||
| Connection side | control side | |
| Connection | terminals 3, 4: | |
| Exit | signal, relay | |
| Contact loading | 253VAC/2A/cos φ>0.7; 126.5VAC/2A/cos φ>0.7; 30VDC/2A resistive load | |
| Minimum switching current | 2 mA / 24 VDC | |
| On/Off Delay | ≤ 20 ms / ≤ 20 ms | |
| Mechanical life | 10 7 switching cycles | |
| Transfer characteristics | ||
| Accuracy | Max. 0.1% of full scale | |
| The influence of ambient temperature | < 100 ppm/K of full-scale value | |
| Galvanic isolation | ||
| Output/power supply | Safe electrical insulation due to reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V, rms test voltage 3 kV, 50 Hz, 1 min. | |
| Input/Other circuits | Safe electrical insulation due to reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V, rms test voltage 3 kV, 50 Hz, 1 min. | |
| Indicators/settings | ||
| Display elements | LEDs | |
| Controls |
DIP switch buttons |
|
| Configuration |
via DIP switches via keys via software |
|
| Marking | marking space at the front | |
| Compliance with directives | ||
| Electromagnetic compatibility |
|
|
|
|
Directive 2014/30/EU | EN 61326-1:2013 (industrial premises) |
| Low voltage |
|
|
|
|
Directive 2014/35/EU | EN 61010-1:2010 |
| Correspondence | ||
| Degree of protection | IEC 60529:2001 | |
| Protection against electric shock | EN 61010-1:2010 | |
| Environmental conditions | ||
| Ambient temperature | -25...70°С (-13...158°F) | |
| Storage temperature | -40...85°С (-40...185°F) | |
| Damaging gas | Designed for use in environmental conditions in accordance with ISA-S71.04-1985, severity level G3 | |
| Mechanical characteristics | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Cross-section of the core | 0.5...2.5 mm2 ( 20...14 AWG) | |
| Weight | approx. 70 g | |
| Dimensions | 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 in) (W x H x D), housing type S1 | |
| Installation | on a 35 mm DIN mounting rail in accordance with EN 60715:2001 | |