Product Description: Disconnect Terminal UT 6-T/SP RD
Product characteristics
| Product type | Disconnect terminal |
| Number of connection points | 2 |
| Number of rows | 1 |
| Potentials | 1 |
| Insulation characteristics | |
| Overvoltage category | III |
| Degree of pollution | 3 |
Electrical characteristics
| Rated impulse voltage | 8 kV |
| Max. power loss under nominal conditions | 1.31 W |
Terminal characteristics
| Number of connection points per tier | 2 |
| Nominal cross-section | 6 mm² |
| 1st tier | |
| Screw threads | M4 |
| Tightening torque | 1.5 ... 1.8 Nm |
| Stripping length | 12 mm |
| Connection according to standard | IEC 60947-7-1 |
| Cross-section of rigid wire | 0.2 mm² ... 10 mm² |
| Conductor size AWG | 24 ... 8 (converted according to IEC) |
| Cross-section of flexible wire | 0.2 mm² ... 10 mm² |
| Flexible conductor cross-section [AWG] | 24 ... 8 (converted according to IEC) |
| Cross-section of flexible conductor (with cable lug without plastic sleeve) | 0.25 mm² ... 6 mm² |
| Cross-section of flexible conductor (with cable lug and plastic sleeve) | 0.25 mm² ... 6 mm² |
| Flexible wire cross-section (2 wires of the same cross-section with a TWIN tip in the form of a plastic sleeve) | 0.25 mm² ... 4 mm² |
| 2 rigid wires of the same cross-section | 0.2 mm² ... 2.5 mm² |
| 2 flexible wires of the same cross-section | 0.2 mm² ... 2.5 mm² |
| 2 flexible conductors of the same cross-section with a cable lug without a plastic sleeve | 0.25 mm² ... 1.5 mm² |
| Rated current | 41 A |
| Maximum load current | 50 A (For cable cross-section of 10 mm²) |
| Nominal voltage | 1000 V (Voltage may decrease due to the use of accessories.) |
| Nominal cross-section | 6 mm² |
Dimensions
| Width | 8.2 mm |
| Lid width | 2.2 mm |
| Height | 105.2 mm |
| Depth on NS 32 | 58 mm |
| Depth on NS 35/7.5 | 53 mm |
| Depth on NS 35/15 | 60.5 mm |