Excerpt from the technical data sheet: Technical data GUB*
| Electrical characteristics | ||
|---|---|---|
| Operating voltage | 1500VDC / 1000VAC max. | |
| Working current | recommended: 1600A max. | |
|
Mechanical characteristics |
||
| Thread type | ISO metric pitch 1.5 mm or NPT ANSI ASME B1.20.1 | |
| Case cover | round threaded cap | |
| Fastening the lid | stream of flame | |
| Lid seal | no, sealing ring for IP66/67 | |
| Degree of protection | IP66 (IP66/67 with sealing ring) | |
| Cable entry | see data table | |
| Material |
|
|
|
|
Frame | aluminum alloy |
|
|
Glass | heat-resistant tempered glass |
|
|
End | epoxy coating RAL 7005 (gray) |
|
|
sealing ring | silicone |
| weight |
see data table , valid for an empty case, will increase depending on the built-in components |
|
| Dimensions |
see data table values may vary slightly due to casting and manufacturing tolerances |
|
| Installation | see data table | |
| Grounding | External grounding points M6 | |
|
Environmental conditions |
||
| Ambient temperature |
-60 ... 60 °C (-76 ... 140 °F) depending on the built-in components |
|
|
Data for use in hazardous areas |
||
| EC Type Examination Certificate |
INERIS 14 ATEX 0035X INERIS 16 ATEX 9005U |
|
|
|
Marking |
II 2 GDEx db IIC T* Gb Ex tb IIIC T** °C Db T6/T85 °C T5/T100 °C T4/T135 °C T3/T200 °C depending on configuration, ambient temperature and built-in power losses |
|
|
Maximum dissipated power |
see data table Maximum dissipated power at T4/+40 °C |
|
International certificates |
||
| IECEx certification |
IECEx INE 14.0042X IECEx INE 16.0051U |
|
| UKCA approval |
CML 21 UKEX 21304X CML 21 UKEX 2976U |
|
| EAC approval | TU RU C-IT.AA87.B.00156 | |
| ECAS approval | 22-09-51658/E22-09-051730/NB0002 | |
| Further statements | available for request | |
|
Correspondence |
||
| Degree of protection | EN 60529 | |
| CE marking | 0080 or 0102, see type plate | |
II 2 GD