Certificates and Conformities
EDSX control stations:
- Class I, Division 2, Groups B, C, D
- Class I, Zone 2, IIA, IIB + H 2
- Class II, Division 1, Groups E, F, G
- Class III
- UL Standards: UL1203, UL121201, UL508
- CSA Standards: C22.2 Nos. 14, 25, 213-17
- NEMA 4X
- Operating temperature range: from -40°C to +60°C
Electronic digital signature control posts:
- Class I, Division 1, Groups C, D
- Class I, Division 2, Groups B, C, D
- Class I, Zones 1 and 2, IIA
- Class I, Zone 2, IIB + H 2
- Class II, Division 1, Groups E, F, G
- Class III
- UL Standards: UL1203, UL121201, UL508
- CSA Standards: C22.2 Nos. 14, 25, 213-17
- NEMA 3
- Operating temperature range: from -25°C to +40°C
EFS Control Posts:
- Class I, Divisions 1 and 2, Groups B, C, D
- Class II, Division 1, Groups E, F, G
- Class II, Division 2, Groups F, G
- Class III
- UL standard: UL1203
- CSA Standard: C22.2 No. 30
- NEMA 3
- Operating temperature range: from -25°C to +40°C
Design Features
- Factory sealing eliminates the need for external sealing fittings required for Class I, Division 1 and 2 environments, reducing installation costs and associated hassles.
- Large mounting screws for securing covers to the body; cover screws are captive on EDSX models
- Mounting eyes and hubs with tapered threads and integrated bushings
- The front button (marked "STOP" and "OFF") and the selector switch covers are locked.
- A 1/4" deadbolt padlock hole is provided when used with front lever and side type covers.
- Front-lever and side-mounted control housings use threaded shafts and bushings to provide hazard protection.
- Dead-end (EDSX, EDS, or EFS) or feed-through (EDSCX, EDSC, or EFSC) hubs - sizes 1/2" to 1"
- Tight tolerances on wide mating flanges and journal shafts and bearings for front button operation ensure fire-tight housing connections.
- When the "STOP" indication is displayed, the button automatically turns red; when the "START" indication is displayed, the button automatically turns green; otherwise, the black buttons are standard.
- Contact Block: 10A @ 600VAC, 5A @ 125VDC
- Indicator Lights: 120V (1.2W LED, 6W Incandescent), Option S300 24V (0.6W LED, 1.7W Incandescent)
Standard materials
- Housings and covers – Feraloy iron alloy with electro-galvanized and aluminum acrylic paint or copper-free aluminum.
- Shafts and shaft bushings – stainless steel
- Handle and button protection – nylon type 6/6