- Switch-disconnectors and safety switches (Ex e) made of fibreglass or stainless steel
DIS* switch-disconnectors and SAF* safety switches, made of glass-fiber-reinforced polyester or stainless steel, can be used in hazardous areas up to Zone 1/21. Various configurations of main and auxiliary contacts meet many switching requirements.
|
Electrical characteristics |
||
|---|---|---|
| Operating voltage | 690 V max. | |
| Rated impulse withstand voltage | 6 kV | |
| Nominal frequency | 50/60 Hz | |
| Short-circuit current limitation |
recommended: 25 A: 35 A, gG 40 A: 63 A, gG |
|
| Working current | 25A max or 40A max | |
| Terminal power | see data table | |
| Nominal insulation voltage | 800 V | |
| Function | switch-disconnector | |
|
|
Color | black and red-yellow |
|
|
Contact configuration | see data table |
|
|
Switching configuration | 2-position switch with left OFF. |
|
|
Category of use | see data table |
|
|
Number of poles | see data table |
|
|
Auxiliary contacts | see data table |
|
|
Auxiliary Contact Usage Category | see data table |
|
|
Operator action | to do - to do |
|
|
Lockable | in the "OFF" position with a triple lock |
|
|
Marking | 0 - I |
|
Mechanical characteristics |
||
| Range of cases | see table | |
| Case cover | completely removable | |
| Fastening the lid | A4 (V4A) stainless steel hex head screws or a combination of stainless steel Phillips head and slot head screws | |
|
|
Screws | M6 |
|
|
Number | 4 |
|
|
Tightening torque | 3.5 Nm |
| Lid seal | foamed silicone | |
| Safety | The cover can only be removed when the actuator is in the "ON" position with SAF.* Options | |
| Degree of protection | IP66 | |
| Cable entry | see data table | |
| Defined entry area | face B | |
| Material |
|
|
|
|
Frame | carbon-containing antistatic polyester reinforced with glass fibre (GRP) or AISI 316L, stainless steel (1.4404) |
|
|
End | own color black or matte |
| weight | see data table | |
| Dimensions | see data table | |
| Tightening torque |
|
|
|
|
Tightening torque of the nuts on the body (SW1) | see cable entry specifications |
| Installation | see data table | |
| Grounding |
GRP is not standard Stainless steel M6 internal/external nickel plated brass earth bolt |
|
|
Environmental conditions |
||
| Ambient temperature | -40...55 °C (-40...131 °F) at T4 | |
|
Data for use in hazardous areas |
||
| EC Type Examination Certificate | CML 16 ATEX 3009X | |
|
|
Marking |
II 2 GDEx db eb IIC T* Gb Ex tb IIIC T** °C Db T4/T130 °C at Ta +55 °C |
|
International certificates |
||
| IECEx certification | IECEx CML 16.0008X | |
| UKCA approval | CML 22 UKEX 2550X | |
| ECAS approval | 22-10-53256/E22-09-052316/NB0002 | |
| internal audit approval | MASK C/18-0003X | |
| CCC approval | 2020322304002545 | |
|
Correspondence |
||
| Degree of protection | EN 60529 | |
| Category of use | IEC/EN 60947 | |
| CE marking | 0080 or 0102, see type plate | |
II 2 GD